Sylk Input/Output Expansion Module with 6 Universal Inputs, 4 Analog Outputs, and 2 Digital Outputs for Spyder Controllers

  • Expands the I/O capacity of a Spyder controller by 8 to 12 points
  • 6 universal inputs for sensors and field devices
  • 4 analog outputs configurable for 0-10 VDC or 4-20 mA
  • 2 triac-type digital outputs, 20-30 VAC at 50/60 Hz
  • Programmed from the Spyder controller itself with its wire sheet
  • Two-wire, polarity-free Sylk bus communication
  • UL plenum-certified enclosure, DIN rail or panel mounting
ModelSIO6042
SAT46171619
3 years of warranty

Sign in to see special prices

Sign in

Specifications

The SIO6042 is a Honeywell Sylk I/O module, designed to integrate with relay-equipped Spyder controllers (models PUL6438SR for LON or PUB6438SR for BACnet) using only Sylk™ communication. It expands the physical input and output capacity of a single Spyder controller, allowing it to be used in HVAC applications where the required number of I/O points is greater than that of a full-size Spyder. The control logic remains in the Spyder controller and is programmed with the same wire sheet, through the Niagara Framework® software.

Key Features

  • Expands the I/O capacity of a Spyder controller by 8 to 12 points
  • 6 universal inputs for sensors and field devices
  • 4 analog outputs configurable for 0-10 VDC or 4-20 mA
  • 2 triac-type digital outputs, 20-30 VAC at 50/60 Hz
  • Programmed from the Spyder controller itself with its wire sheet
  • Two-wire, polarity-free Sylk bus communication
  • UL plenum-certified enclosure, DIN rail or panel mounting

Technical Specifications

UNIVERSAL INPUTS6
ANALOG OUTPUTS4, 0-10 VDC or 4-20 mA (max. load 550 Ω)
DIGITAL OUTPUTS2, triac, 20-30 VAC, 25-500 mA continuous
POWER SUPPLY20-30 VAC, 50/60 Hz, max. consumption 5 VA
COMMUNICATIONSylk bus, polarity-free
COMPATIBILITYSpyder PUL6438SR (LON) or PUB6438SR (BACnet)
MOUNTINGDIN rail or panel, UL plenum enclosure