PROFINET IO Fieldbus Coupler / 3rd Generation Advanced / Integrated 2-Port Switch / 250 Modules per Node / 512 Bytes I/O / PROFIsafe V2 PROFIenergy V1.0 / IP20
- PROFINET IO with integrated 2-port switch
- Support for up to 250 modules per node
- Transmission speed 10/100 Mbit/s full duplex
- Isochronous real-time (IRT) communication
- 500 kV isolation between system and field
- Compatibility with PROFIsafe V2 and PROFIenergy
Sign in to see special prices
Sign inSign in to see special prices
Sign inSpecifications
WAGO
Model: 750-375
Third-generation Advanced PROFINET IO fieldbus coupler for the WAGO I/O SYSTEM 750. It features an integrated 2-port RJ-45 switch, allowing line topology without an external switch, and automatically recognizes connected I/O modules up to 250 per node. It handles a process image of 512 input bytes and 512 output bytes at 10/100 Mbit/s, with 1, 2, and 4 ms IRT isochronous communication. It supports PROFIsafe V2 and PROFIenergy V1.0, and device replacement is performed without a programming tool.
Features
- Protocol: PROFINET IO with 2-port switch
- Scalability: Up to 250 modules per node
- Process image: 512 input bytes and 512 output bytes
- Real time: IRT isochronous communication from 1 ms
- Profiles: PROFIsafe V2 and PROFIenergy V1.0
- Power supply: 24 VDC with 500 V isolation
250
A single coupler organizes the entire I/O island of the cabinet.
512 bytes of process image per directionTechnical Specifications
Communication
- Protocol: PROFINET IO
- Profiles: PROFIsafe V2 / PROFIenergy V1.0
- Switch: 2 integrated ports
- Speed: 10/100 Mbit/s
- Bus segment: 328 ft (100 m)
- Medium: S-UTP 100 Ω cat. 5 twisted pair
- Modules per node: 250 max. / 64 without extension
- Process image: 512 / 512 bytes
- Clock: 1 ms (RT) / 1, 2, 4 ms (IRT)
- Auto-MDIX: Yes
Power Supply
- System: 24 VDC (-25 to +30 %)
- 5 V consumption: 450 mA
- Total system current: 1700 mA
- Field: 24 VDC (-25 to +30 %)
- Input current: 500 mA at 24 V
- Supply efficiency: 90 % at 24 V
- Isolation: 500 V system/field
- Power contacts: 3 / 10 A
Connections
- Fieldbus: 2 x RJ-45
- Field power: 6 x CAGE CLAMP®
- System power: 2 x CAGE CLAMP®
- Configuration: 1 4-pole male connector
- Conductor: 0.08 to 2.5 mm² (28 to 14 AWG)
- Strip length: 0.31 to 0.35 in (8 to 9 mm)
- Mounting: DIN-35 rail
Physical and Environment
- Dimensions: 2.4 x 3.9 x 2.8 in (61.5 x 100 x 71.9 mm)
- Depth from rail: 2.5 in (64.7 mm)
- Weight: 5.34 oz (151.5 g)
- Housing: Polycarbonate / polyamide 6.6
- Protection: IP20 / pollution degree 2
- Operation: 0 to +131 °F (55 °C)
- Storage: -25 to +185 °F (85 °C)
- Humidity: 95 % non-condensing
- Vibration / shock: 4g / 15g
- Gases: H2S 10 ppm / SO2 25 ppm at 75 % RH
On the PROFINET Network
The coupler presents itself as an I/O device on the network and builds the local process image with the modules to its right, mixing analog and digital modules without additional configuration. With two RJ-45 ports, the daisy-chain line can be closed and the next node connected to the same switch, without intermediate equipment. If a coupler fails, replacement is done without software: the controller recognizes the island again and the rest of the cabinet remains the same.